Metal-clad switchgear, SF6 / vacuum / gas-insulated ring main units and solid-insulated cubicles for 12–40.5kV distribution networks.
Jingmin Electric supplies two families of medium voltage switchgear: metal-clad withdrawable switchgear for distribution rooms and substations, and ring main units (RMUs) for compact ring networks, wind farms, underground substations and outdoor enclosures.
All enclosures, busbars, mechanisms and secondary wiring are made in our own workshops. Interrupters and instrument transformers fitted inside are also our own production — which is why we can offer both competitive pricing and short lead times on custom schemes.
The workhorse of 12 kV distribution rooms — withdrawable handcart, independent pressure relief, cable or busbar compartment options.
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 / 60 |
| Power-frequency withstand voltage (1 min) | kV | 42 (phase–earth / phase–phase) |
| Lightning impulse withstand voltage | kV | 75 |
| Rated current | A | 630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000 |
| Rated short-circuit breaking current | kA | 20 / 25 / 31.5 / 40 |
| Rated short-time withstand current (4 s) | kA | 20 / 25 / 31.5 / 40 |
| Rated peak withstand current | kA | 50 / 63 / 80 / 100 |
| Busbar arrangement | — | Single or double busbar |
| Degree of protection | — | IP4X (enclosure), IP2X (door open) |
| Typical dimensions W × D × H (1250 A) | mm | 800 × 1500 × 2300 |
| Ambient temperature | °C | −15 to +40 |
| Standards | — | IEC 62271-200, GB 3906 |
Dimensions vary with rated current, busbar arrangement and cable compartment. Special widths available for 3150 A and 4000 A schemes.
Busbar compartment, handcart (breaker) compartment, cable compartment and LV compartment, each pressure-relieved independently.
Breaker cannot be racked in or out with the door open or the earthing switch open — mechanical and electrical interlocks as standard.
VS1 / ZN63A indoor vacuum circuit breaker as standard; other compatible withdrawable units on request.
40.5 kV withdrawable switchgear for sub-transmission and large plants; fixed-type cubicles where the budget or floor space demands a simpler scheme.
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage | kV | 40.5 |
| Power-frequency withstand voltage (1 min) | kV | 95 |
| Lightning impulse withstand voltage | kV | 185 |
| Rated current | A | 1250 / 1600 / 2000 / 2500 |
| Rated short-circuit breaking current | kA | 20 / 25 / 31.5 |
| Rated short-time withstand current (4 s) | kA | 20 / 25 / 31.5 |
| Rated peak withstand current | kA | 50 / 63 / 80 |
| Typical dimensions W × D × H | mm | 1400 × 2800 × 2600 (single busbar) |
| Standards | — | IEC 62271-200, GB 3906 |
| Parameter | Unit | Value |
|---|---|---|
| Rated voltage | kV | 12 |
| Power-frequency withstand voltage (1 min) | kV | 42 |
| Lightning impulse withstand voltage | kV | 75 |
| Rated current | A | 630 / 1250 |
| Rated short-circuit breaking current | kA | 20 / 25 |
| Rated short-time withstand current (4 s) | kA | 20 / 25 |
| Typical dimensions W × D × H | mm | 1000–1200 × 1200 × 2650 |
| Busbar | — | Single busbar, top or bottom entry |
| Standards | — | IEC 62271-200, GB 3906 |
Modular, extendable or sealed-for-life — choose the insulation technology that suits your climate, maintenance policy and procurement rules.
| Model | Insulation | Rated voltage | Rated current | Short-circuit (3–4 s) | Switching device |
|---|---|---|---|---|---|
| HXGN15-12 | SF6 | 12 kV | 630 A | 20 kA | SF6 load break switch / vacuum CB (V module) |
| HXGN17-12 | Air / vacuum | 12 kV | 630 A | 20 kA | Vacuum load break switch |
| RM6-12 / RM6-24 | Sealed SF6 | 12 / 24 kV | 630 A | 20 kA | SF6 LBS + vacuum CB |
| LPG-12 | Solid (epoxy) | 12 kV | 630 A | 20 kA | Vacuum, fully sealed, maintenance-free |
| XGN-12/630 | SF6-free eco-gas (dry air / N₂) | 12 kV | 630 A | 20 kA | Vacuum |
| XGW-12 | SF6 or solid | 12 kV | 630 A | 20 kA | Vacuum, with FTU / DTU for automation |
| HWX-12 | Air | 12 kV | 630 A | 20 kA | Outdoor switching station, 2–4 ways |
Ring main units are described by their module chain, e.g. C–F–V–C:
Three points decide most RMU choices:
Tell us the rated voltage, busbar current, short-circuit level, number of feeders and whether you need cable or busbar entry. We will come back with a scheme drawing and a price.