🏭 Manufacturer since 2013 · IEC / GB Standards · OEM & ODM Welcome
📧 sales@jingminelectric.com  |  📱 WhatsApp / WeChat: +86 130 9198 8913

Vacuum Circuit Breakers & Switching Devices

Indoor and outdoor vacuum circuit breakers, load break switches, disconnectors and fuses for line protection and sectionalizing.

Overview

Vacuum circuit breakers are the core of our component business. We manufacture our own vacuum interrupters, cast-resin poles, spring operating mechanisms and controllers — which is why our breakers go into our own switchgear, into panel builders' assemblies, and onto distribution poles in a dozen countries.

  • Outdoor pole-mounted, outdoor tank type and indoor withdrawable designs
  • 12 kV, 24 kV and 40.5 kV
  • Manual, motorised / spring-charged and intelligent (recloser) versions
  • Compatible with RTU / FTU for distribution automation
  • Companion devices: load break switches, disconnectors, earthing switches, drop-out fuses
Spare parts support: vacuum interrupters, contact arms, operating coils, auxiliary contacts and mechanism kits are available for the models we supply.

Documents supplied: routine test report, mechanical characteristic curve, wiring diagram, installation manual.

Outdoor Vacuum Circuit Breakers

Pole-mounted and tank-type breakers for overhead lines, rural networks, construction sites and small substations.

ZW32-12 / ZW32-12F — pole-mounted outdoor VCB (typical data)
ParameterUnitValue
Rated voltagekV12
Power-frequency withstand voltage (1 min)kV42
Lightning impulse withstand voltagekV75
Rated currentA630 (1250 available)
Rated short-circuit breaking currentkA20 (25 available)
Rated short-time withstand current (4 s)kA20
Rated peak withstand / making currentkA50
Rated operating cycles (mechanism)times10 000
Mechanical life of vacuum interruptertimes10 000 operations, 20 breaking operations at rated current
Operating mechanism—Spring-charged; manual, motor or remote
Control voltageVDC 24 / 48 / 110 / 220 or AC 220
Degree of protection—IP54 (typical, pole-mounted enclosure)
Ambient temperature°C−40 to +40
Standard—IEC 62271-100, GB 1984
ZW7-40.5 & ZW8-12 — outdoor VCB (typical data)
ModelRated voltageRated currentBreaking currentTypical application
ZW7-40.540.5 kV1250 / 1600 / 2000 A25 / 31.5 kA35 kV overhead lines, substation incomers, sectionalizing
ZW8-1212 kV630 / 1250 A20 / 25 kAOutdoor pole-mounted, integrated with disconnect and CT
ZW32-12F12 kV630 A20 kAIntelligent recloser with FTU, auto-reclosing & fault isolation

Indoor Vacuum Circuit Breakers

Withdrawable handcart and fixed units for metal-clad switchgear, ring main units and motor control.

ZN63A (VS1)-12 / ZN85-40.5 — indoor VCB (typical data)
ParameterUnitZN63A (VS1)-12ZN85-40.5
Rated voltagekV1240.5
Power-frequency withstand (1 min)kV4295
Lightning impulse withstandkV75185
Rated currentA630 / 1000 / 1250 / 1600 / 2000 / 2500 / 3150 / 40001250 / 1600 / 2000 / 2500
Rated short-circuit breaking currentkA20 / 25 / 31.5 / 4020 / 25 / 31.5
Rated short-time withstand (4 s)kA20 / 25 / 31.5 / 4020 / 25 / 31.5
Rated peak withstandkA50 / 63 / 80 / 10050 / 63 / 80
Mechanical lifeoperations10 000 (20 000 optional)10 000
Rated short-circuit breaking operationstimes5030
Installation—Withdrawable handcart (fixed type available)Withdrawable handcart
Standard—IEC 62271-100, GB 1984IEC 62271-100, GB 1984

Breakers can be supplied loose for your own switchgear, or factory-fitted and tested inside ours — whichever suits your scope.

Switching & Protection Devices

The rest of the line-hardware package — usually ordered together with the breakers.

Load break switches, disconnectors and earthing switches (typical data)
ModelTypeRated voltageRated currentNotes
FN7-12 / FZN21-12Indoor load break switch12 kV400 / 630 AWith or without integral earthing switch and fuse
GW4-12 / GW4-40.5Double-column outdoor disconnector12 / 40.5 kV630–1250 AManual or motorised, with earthing blade option
GW5-40.5V-shaped outdoor disconnector40.5 kV630–1250 ACompact, for substation busbar isolation
GW9-12Single-column outdoor disconnector12 kV200–630 APole-mounted line isolation
JN15-12Indoor earthing switch12 kV—Short-circuit making capacity 50 kA peak
Fuses (typical data)
ModelTypeVoltageCurrent rangeTypical use
RW12-12Outdoor drop-out fuse12 kV5–200 APole-mounted transformer protection
XRNT / XRNPIndoor current-limiting fuse12–40.5 kV6.3–200 ASwitch–fuse combinations, voltage transformer protection
RN2-10Indoor PT protection fuse10 kV0.5–5 AVoltage transformer protection
NT / RTLV HRC fuseup to 690 V2–1250 ALV distribution and motor protection

Need a Breaker Quotation or a Sample?

Tell us the model, rated voltage, current and operating mechanism (manual, motor or intelligent). Mixed orders with switchgear and components are welcome.

Chat on WhatsApp